Function and purpose
The modular power quality power unit adopts the latest power electronic converter technology, combined with efficient software control algorithms, to achieve diversified power quality optimization functions. Power units with different functions can independently implement reactive power compensation, harmonic filtering, and three-phase unbalance management according to needs. They can also achieve multi-functional combinations to meet the needs of different capacities and different environments, and provide multiple solutions to solve power quality problems.
Detailed description
Parameters:
Rated capacity of single machine: APF(A):50/75/100/150
SVG(kvar): 50/100
Machine efficiency: ≥95%
Dynamic response time: ≤100us
Full response time: ≤10ms
Advantages/core functions:
01 Small size
The module adopts 520 width, which can be adapted to 600/800/1000 wide cabinets
The depth is only 440, suitable for 600mm deep compensation cabinets
The capacity of a single cabinet can reach up to 600kVar\900A, suitable for more scenarios
02 Strong heat dissipation
The two parts of power electronics are effectively isolated, and the upper and lower layers adopt a unique air duct design to effectively deal with ventilation and heat dissipation problems
The radiator material adopts the shovel tooth process, and the heat dissipation performance is stable, ensuring product operation efficiency and reducing the failure rate
03 Easy installation
Network side or load side CT sampling can be carried out according to specific conditions, and settings can be made through a dedicated controller to help with quick installation
Detailed parameters
Noise indexFault record
| Parameter classification< /th> | Parameter items | Parameter values |
|---|
| System parameters | Product model | NXWAPF |
| Rated input line voltage | 400V±20% |
| Grid frequency | 50Hz (±5 %) |
| Overall efficiency | ≥97% |
| Current transformer | Secondary rated current 5 a 75A 100A 150A |
| Reactive power compensation | Supported |
| Harmonic filtering | Supported |
| Three-phase unbalance management | Support |
| Low voltage ride through | Support |
| Filtering range | 2~25 Times |
| Filtering times selection | 2~25 Times |
| Filter compensation rate | ≥95% |
| Fast response time | 10 0us |
| Full response time | 10ms |
| Control algorithm | Intelligent FFT, instantaneous reactive power |
| Cooling method | Intelligent air cooling (automatic fan speed adjustment) |
| ≤60dB |
| Communication | Communication interface | RS485, Bluetooth, GPRS (optional) |
| Communication protocol | Modbus |
| Protection function | System voltage overvoltage and undervoltage protection | Support |
| Compensation output automatic current limiting | Support |
| Compensation output over-current protection | Support |
| Over-temperature protection | Support |
| DC side bus overvoltage and undervoltage protection Protection | Support |
| Control system failure | Support |
| Main circuit device Damage protection | Supported |
| Automatic detection of voltage and current phase sequence | Supported |
| Support |
| Installation | Installation method | Rack-mounted |