Function and purpose
Provides various protections such as overload long delay, short circuit short delay, short circuit instantaneous etc.
Detailed description
Parameters:
Maximum Icu: 70kA
Working voltage: AC230V/240V, 400V/415V, 500V, 690V
Using ambient temperature: -25°C~+70°C
Advantages/core functions:
01 Comprehensive functions
Can carry out overload long-delay, short-circuit short-delay, short-circuit instantaneous and other protections, and also has overload alarm non-trip function to meet various customer protection needs
02 Safe and reliable
Higher rated insulation voltage and rated impulse withstand voltage, safer for customers to use
03 Flexible and easy to use
Universal design of internal accessories reduces customer stocking types and helps customers save inventory
Detailed parameters
< td>*
| Parameter classification | Parameter items | Parameter values |
|---|
| System parameters | Rated operating current In(A) | 160: 32, 63, 100, 125, 160 250: 200, 250 400: 300, 315, 320, 400 630: 500, 630 1000: 630, 800, 1000 1250: 1000 1600: 1000 |
| Rated insulation voltage Ue(V) | 800: 8 1000: 12 |
| Rated impulse withstand voltage Uimp(kV) | AC 50/60Hz: 8 AC 50/60Hz: 12 * 3P: * |
| Rated making and breaking capacity Icu(kA) | AC230/240V: 75 AC400/415V: 50 AC500V: 30 AC690V: 10 |
| Rated operating short-circuit breaking capacity Ics(kA) | AC230/240V: 50 AC400/415V: 50 AC500V: 30 AC690V: 5 |
| Rated limited short-circuit current Icw(A) | 1s: 1 3s: - 6s: 6 |
| Comply with standards | IEC/EN 60947-2, GB/T 14048.2 |
| Usage category | A: Maintenance-free A: Maintenance required B: With maintenance |
| Isolation function | * |
| Ambient air temperature | -25℃~+70℃ |
| Performance index | Flashover distance | ≤ 50: 20000 times ≤ 50: 20000 times ≤ 100: 40000 times ≤ 100: 20000 times ≤ 100: 10000 times ≤ 100: 5000 times ≤ 100: 5000 times ≤ 100: 10000 times ≤ 100: 10000 times ≤ 100: 2500 times ≤ 100: 2500 times |
| Mechanical life (times) | AC415V, In: 10000 times AC415V, In: 10000 times AC415V, In: 8000 times AC415V, In: 8000 times AC415V, In: 2500 times AC415V, In: 2500 times |
| Electrical life (times) | Distribution protection: * Motor protection: * Fuse protection: * Isolating contact: * Separating contact: * Undervoltage release: * Communication module: * Manual operating mechanism: * Electric operating mechanism: * Plug-in type: * Same rating: * Interlocking plate: * Manual test module: * |
| Electronic tripping (adjustable) | * |
| Communication | |
| Protection function | | * |
| Installation | Outline dimensions (mm) (W×H×D) | 90/120: 155 105/140: 165 140/185: 257 140/185: 257 210/280: 280 210/280: 370 210/280: 370 1250/153/153, 1600: 158/158 |
| Deep (S type/H type) | √/√1: 108.5/108.5 108.5/108.5: 118/118 153/153: 1250/153/153, 1600: 158/158 |