Function and use
NXMN Kunlun series transparent case plastic case circuit breakers provide protection for lines and equipment in distribution lines when overload, short circuit, and undervoltage occur, and can also provide overload, short circuit, and undervoltage protection for infrequent starting of motors.
Detailed parameters
< /tr>< td>Breaking capacity< td>Motor protection< /tr>< td>Arc isolation plate3P
| Parameter classification | Parameter item | Parameter value |
|---|
| Product model | NXMN-63 | 10-16-20-32-40-50-63 |
| NXMN-125 | 10-16-20-32-40-50-63-80-100-125 |
| NXMN-160(W125) | 160/20/32-40-50-63-80-100-125-160 W125/16-20-32-40-50-63-80-100-125 |
| Electrical performance | Rated operating current I(A), 40℃ | |
| Rated insulation voltage Ui (V) | 800 |
| Rated impulse withstand voltage Uimp (kV) | 8 |
| Rated operating voltage Ue(V),AC 50/60Hz | AC 220/230/240, 380/400/415, 660/690 |
| Number of poles | 2P | ■ |
| 3P | ■ |
| 4P | ■ |
| AC220/230/240V | S |
| AC380/400/415V | S |
| AC660/690V | S |
| Rated limit short circuit breaking capacity Icu(kA) | AC220/230/240V | 36 |
| AC380/400/415V | 36 |
| AC660/690V | 5 |
| Rated operating short-circuit breaking capacity Ics(kA) | AC220/230/240V | 18 |
| AC380/400/415V | 15 |
| AC660/690V | 3 |
| Comply with standards | | IEC/EN 60947-2,GB/T 14048.2 |
| Selective category | | A |
| Working environment temperature (℃) | | -35~+70 |
| Isolation function | | ■ |
| Wiring method | | Top in and bottom out |
| Flashover distance (mm) | | ≤ 50 |
| Mechanical life / time | With maintenance | 40000 |
| No maintenance | 20000 |
| Electrical life / Times | AC415V | 10000 |
| Thermal magnetic tripper | Power distribution protection | ■ |
| ■ |
| Generator protection | ■ |
| Single magnetic release | Distribution protection | ■ |
| Motor protection | ■ |
| Generator protection | ■ |
| Fixed | Front connection | ■ |
| Installation method | | |
| Internal accessories | Split excitation | ■ |
| Auxiliary | ■ |
| Alarm | ■ |
| Auxiliary report | ■ |
| Undervoltage | ■ |
| External accessories | ■ |
| Terminal cover | ■ |
| Connection plate | ■ |
| Hand operation | ■ |
| Handle lock | ■ |
| Outline dimensions (mm) Height (H) × Width (W) × Depth (D) | 2P | 130*52*62 |
| 130*75*62 |
| 4P | 130*100*6 2 |
| | 155*92*72 |
| | 155*122*72 |
| Note: 1. The isolation function is not applicable to circuit breakers with 4A/4D poles. | | |