NM8N series plastic case circuit breaker

Product category:
Molded case circuit breaker
Product code:
P-269
Model:
NM8N

Function & Use (Application Scenarios)

Distribution appliances and plastic case circuit breaker products are mainly suitable for making, breaking and sustaining circuits with AC 50/60Hz, rated voltage AC690V and below, and DC system rated voltage DC1000V and below, rated current 16A to 1600A.

Surprise on inquiry

Product highlights

  • Reliable overload protection
  • Short circuit protection capability
  • Strong breaking ability
  • Easy to install and maintain
  • Modular design

Model

NM8N

Main Product Parameters

ClassificationswitchgearSecondary classificationMolded case circuit breaker
parametersOperating breaking capacity: Ics=100%Icu; rated insulation voltage: 1000V; rated operating current: 16-1600A; operating ambient temperature: -40°C~+70°CAdvantages/core features01 Safe and reliable; the breaking capacity can reach up to 150kA, Ics=100%Icu, and the fault current can be cut off safely; the insulation voltage can reach AC1000V, making operation more reliable in high-altitude environments; 02 Excellent performance; the rated impact withstand voltage is up to 12kV, with higher impact performance; the working environment temperature is -40°C~+70°C, adapting to more harsh environments; 03 Easy to use; electronic two-component motor protection solution can reduce cabinet design space and make installation more convenient; internal accessories can be installed in a modular manner for easy maintenance and replacement

Product details

Function and use

NM8N series plastic case circuit breakers are suitable for making, breaking and carrying rated current in circuits with AC 50/60Hz, rated voltage AC690V and below, and DC system rated voltage DC1000V and below, rated current 16A to 1600A, and can reliably protect lines and electrical equipment in the event of overload, short circuit or undervoltage. It can also be used as infrequent starting and overload, short circuit, and undervoltage protection of the motor.

Detailed description

Parameters:
Operating breaking capacity: Ics=100%Icu
Rated insulation voltage: 1000V
Rated operating current: 16-1600A
Using ambient temperature: -40°C~+70°C

Advantages/core functions:
01 Safe and reliable
The breaking capacity can reach up to 150kA, Ics=100%Icu, and the fault current can be cut off safely

The insulation voltage can reach AC1000V, and the operation is more reliable in high altitude environments
02 Excellent performance
The rated impact withstand voltage is up to 12kV, and the impact performance is higher

The working environment temperature is -40°C~+70°C, adaptable to more harsh environments
03 Easy to use
The electronic two-component motor protection solution can reduce the cabinet design space and make installation more convenient

The internal accessories realize modular installation for easy maintenance and replacement

Detailed parameters

Parameter classificationParameter itemParameter value
System parameterRated operating current In(A),40℃125, 250, 400, 630, 800, 1600
Electronic1.5-2.5-6-10-12.5-16-20-25-32-40-50-63-80-100-125, 125-160-180-200-225-250, 250-315-350-400, 400-500, 500-630-700-800, ——
Thermomagnetic16-20-25-32-40-50-63-80-100-125, 125-160-180-200-225-250, 250-315-350-400, 400-500-630, 500-630-700-800, 800-1000-1250-1600
32-63-100-125, 400-630, 630-800, 800-1000-1250-1600
Electrical propertiesRated insulation voltage Ui (V)1000, 1000, 1000, 1000, 1000, 1000
Rated impulse withstand voltage Uimp (V)8, 8, 12, 12, 12, 12
Rated operating voltage Uimp (V), AC 50/60Hz380/400/415,440,500,660/690, 380/400/415,440,500,660/690, 380/400/415,440,500,660/690, 380/400/415,440,500,660/690, 380/400/415,440,500,660/690, 380/400/415,440,500,660/690
Analytical capability code1PC, S, Q, H, R
2PC, S, Q, H, R
3PC, S, Q, H, R
4PC, S, Q, H, R
Number of polesAC220/230/240V36, 50, 36, 50, 36, 50, 36, 50, 36, 50, 36, 50
AC380/400/415V36, 50, 70, 100, 150, 36, 50, 70, 100, 150, 36, 50, 70, 100, 150, 36, 50, 70, 100, 150, 36, 50, 70, 100, 150, 36, 50, 70, 100, 150
AC440V36, 50, 70, 100, 150, 36, 50, 70, 100, 150, 36, 50, 70, 100, 150, 36, 50, 70, 100, 150, 36, 50, 70, 100, 150, 36, 50, 70, 100, 150
AC500V25, 40, 40, 50, 10, 25, 40, 40, 50, 10, 25, 40, 40, 50, 10, 25, 40, 40, 50, 10, 25, 40, 40, 50, 10, 25, 40, 40, 50, 10
AC660/690V6, 8, 8, 10, 6, 8, 8, 10, 6, 8, 8, 10, 6, 8, 8, 10, 6, 8, 8, 10, 6, 8, 8, 10, 6, 8, 8, 10, 6, 8, 8, 10
Rated ultimate short-circuit breaking capacity Icu(A)36, 50, 36, 50, 36, 50, 36, 50, 36, 50, 36, 50
Rated operating short-circuit breaking capacity Ics(A)36, 50, 70, 100, 150, 36, 50, 70, 100, 150, 36, 50, 70, 100, 150, 36, 50, 70, 100, 150, 36, 50, 70, 100, 150, 36, 50, 70, 100, 150
Rated residual operating current IΔn (A)1032A, 632A, 100A, 160A, 3(250A)
Comply with standardsIEC/EN 60947-2, GB/T 14048.2, IEC/EN 60947-2, GB/T 14048.2, IEC/EN 60947-2, GB/T 14048.2, IEC/EN 60947-2, GB/T 14048.2, IEC/EN 60947-2, GB/T 14048.2, IEC/EN 60947-2, GB/T 14048.2
Use CategoryAA, A (thermal magnetic type) (electronic type), A (thermal magnetic type) (electronic type), A (thermal magnetic type) (electronic type), A (thermal magnetic type) (electronic type)
Working environment temperature-40℃~+70℃-40℃~+70℃, -40℃~+70℃, -40℃~+70℃, -40℃~+70℃, -40℃~+70℃
Isolation functionNone, none, none, none, none
Arc flashover distance00, 0, 0, 0, 0
Mechanical life (times)Maintenance-free25000, 25000, 30000, 20000, 20000, 10000
AC415Vjn 10000, 8000, 8000, 8000, 10000

Requirement confirmation

Application, rating, quantity and drawings are checked first.

Factory matching

Supplier capacity, certificates and production slot are reviewed.

Order transaction

Confirm commercial terms, sign the commercial contract, and confirm the related document checklist.

Shipment control

Packing photos, inspection records and delivery status are tracked.