| 4.1 Rating of circuit breaker (see table 2) | Model | NM1-63S |
| Frame rating rated current (A) | 63 |
| Rated operating voltage Ue(V) | 240/415 |
| Rated insulation voltage Ui(V) | 800 |
| Rated impulse withstand voltage Uimp (kV) 8 | 18/13/- |
| Maintainable mechanical life (times) | 20000 |
| Electrical life AC400V (times) | 3000 |
| Number of poles | 3, 4 |
| Arc distance (mm) | ≤50 |
| Model | NM1-63H |
| Frame grade rated current (A) | 63 |
| Rated operating voltage Ue(V) | 400 |
| Rated insulation voltage Ui(V) | 500 |
| Rated impulse withstand voltage Uimp (kV) | 8 |
| Rated ultimate short-circuit breaking capacity (kA) 240V/415V/690V | -/50+/- |
| Rated operating short-circuit breaking capacity (kA) 240V/415V/690V | -/25+/- |
| Maintainable mechanical life (times) | 20000 |
| Electrical life AC400V (times) | 3000 |
| Number of poles | 2, 3, 4 |
| Arc distance (mm) | ≤50 |
| Model | NM1-125S |
| Frame rating rated current (A) | 125 |
| Rated operating voltage Ue(V) | 240/415/690 |
| Rated insulation voltage Ui(V) | 800 |
| Rated impulse withstand voltage Uimp (kV) | 8 |
| Rated ultimate short-circuit breaking capacity (kA) 240V/415V/690V | 50/35/8 |
| Rated operating short-circuit breaking capacity (kA) 240V/415V/690V | 30/18/4 |
| Maintainable mechanical life (times) | 20000 |
| Electrical life AC400V (times) | 3000 |
| Number of poles | 2, 3, 4 |
| Arc distance (mm) | ≤50 |
| Model | NM1-125H |
| Frame rating rated current (A) | 125 |
| Rated operating voltage Ue(V) | 400/690 |
| Rated insulation voltage Ui(V) | 800 |
| Rated impulse withstand voltage Uimp (kV) | 8 |
| Rated ultimate short-circuit breaking capacity (kA) 240V/415V/690V | -/50/10 |
| Rated operating short-circuit breaking capacity (kA) 240V/415V/690V | -/25/5 |
| Maintainable mechanical life (times) | 20000 |
| Electrical life AC400V (times) | 3000 |
| Number of poles | 2, 3, 4 |
| Arc distance (mm) | ≤50 |
| Model | NM1-125R |
| Frame rating rated current (A) | 125 |
| Rated operating voltage Ue(V) | 400/690 |
| Rated insulation voltage Ui(V) | 800 |
| Rated impulse withstand voltage Uimp (kV) | 8 |
| Rated ultimate short-circuit breaking capacity (kA) 240V/415V/690V | -/85/20 |
| Rated operating short-circuit breaking capacity (kA) 240V/415V/690V | -/42.5/10 |
| Maintainable mechanical life (times) | 20000 |
| Electrical life AC400V (times) | 3000 |
| Number of poles | 3 |
| Arc distance (mm) | ≤50 |
| Model | NM1-250S |
| Frame rating rated current (A) | 250 |
| Rated operating voltage Ue(V) | 240/415/690 |
| Rated insulation voltage Ui(V) | 800 |
| Rated impulse withstand voltage Uimp (kV) | 8 |
| Rated ultimate short-circuit breaking capacity (kA) 240V/415V/690V | 50/35/8 |
| Rated operating short-circuit breaking capacity (kA) 240V/415V/690V | 30/18/4 |
| Maintainable mechanical life (times) | 20000 |
| Electrical life AC400V (times) | 3000 |
| Number of poles | 2, 3, 4 |
| Arc distance (mm) | ≤50 |
| Model | NM1-250H |
| Frame rating rated current (A) | 250 |
| Rated operating voltage Ue(V) | 125, 160, 200, 225, 250 |
| Rated insulation voltage Ui(V) | 400/690 |
| Rated impulse withstand voltage Uimp (kV) | 8 |
| Rated ultimate short-circuit breaking capacity (kA) 240V/415V/690V | -/50/10 |
| Rated operating short-circuit breaking capacity (kA) 240V/415V/690V | -/25/5 |
| Maintainable mechanical life (times) | 20000 |
| Electrical life AC400V (times) | 3000 |
| Number of poles | 2, 3, 4 |
| Arc distance (mm) | ≤50 |
| Model | NM1-250R |
| Frame rating rated current (A) | 250 |
| Rated operating voltage Ue(V) | 125, 160, 200, 225, 250 |
| Rated insulation voltage Ui(V) | 400/690 |
| Rated impulse withstand voltage Uimp (kV) | 8 |
| Rated ultimate short-circuit breaking capacity (kA) 240V/415V/690V | -/85/20 |
| Rated operating short-circuit breaking capacity (kA) 240V/415V/690V | -/42.5/10 |
| Maintainable mechanical life (times) | 20000 |
| Electrical life AC400V (times) | 3000 |
| Number of poles | 3 |