DZ20 series plastic case circuit breaker

Product category:
Molded case circuit breaker
Product code:
P-274
Model:
DZ20

Function & Use (Application Scenarios)

Distribution appliances and plastic case circuit breaker products are mainly suitable for use (hereinafter referred to as circuit breakers). Their rated insulation voltage is 800V, AC 50Hz, rated working voltage is 400V and below, and their rated current ranges from 32A to 1250A. Generally used for power distribution, among which type C

Surprise on inquiry

Product highlights

  • Engineering application adaptation
  • Stable and reliable operation
  • Easy system integration

Model

DZ20

Main Product Parameters

ClassificationswitchgearSecondary classificationMolded case circuit breaker

Product details

Function and use

DZ20 series plastic case circuit breaker (hereinafter referred to as circuit breaker) has a rated insulation voltage of 800V, AC 50Hz, a rated working voltage of 400V and below, and a rated current from 32A to 1250A. Generally used for power distribution, the rated current of type C is 160A, and the circuit breakers of type 630 and below can also be used to protect motors. Under normal circumstances, the circuit breaker can be used for infrequent switching of circuits and infrequent starting of motors respectively.

Detailed parameters

Parameter table 1

Parameter classificationParameter itemParameter value
3.1 Main technical parameters of the circuit breaker (see table 2)ModelDZ20Y-100, DZ20C-160, DZ20Y-225, DZ20Y-400, DZ20Y-630, DZ20Y-1250
Number of poles3P
Rated operating voltage Ue (V)400, 400, 400, 380, 380, 380
Rated insulation voltage Ue (V)800
Short circuit breaking capacity kA (effective value) Icu/cosΦ18/0.30, 12/0.30, 25/0.25, 30/0.25, 30/0.25, 50/0.25
Short circuit breaking capacity kA (effective value) Ics/cosΦ14/0.30, 8/0.5, 19/0.30, 23/0.25, 23/0.25, 32.5/0.25
Rated circuit breaker current In A32, 40, 50, 63, 80, 100; 100, 125, 160; 125, 160, 180, 200, 225; 250, 315, 350, 400; 500, 630; 800, 1000, 1250
Number of operating cyclesWith load: 1500, 1000, 1000, 1000, 1000, 500; No load: 8500, 7000, 7000, 4000, 4000, 2500
Operation frequency / hour120, 120, 120, 60, 60, 20
Arc distance mm50, 50, 50, 100, 100, 120
3.2 Circuit breaker short-circuit protection current setting value (see table 3)Model numberDZ20Y-100, DZ20C-160, DZ20Y-225, DZ20Y-400, DZ20Y-630, DZ20Y-1250
Instantaneous operating current setting value of distribution circuit breaker Ii(A) and toleranceIn ≤ 40A: 500, ±20%; In> 40A: 10In, ±20%; 10In, ±20%; 10In, ±20%; 10In, ±20%; 7In,±20%
Instantaneous operating current setting value Ii (A) and tolerance of circuit breaker for motor protectionIn ≤ 40A: 600, ±20%; In>40A: 12In, ±20%; 12In, ±20%; 12In, ±20%; 12In,±20%; -
Single-pole short-circuit protection current action setting value Ii(A)For power distribution: In ≤ 40A: 700; In > 40A: 14In; For motor protection: In ≤ 40A: 850; In > 40A: 17In; For power distribution: 14In; For motor protection: 16In; For power distribution: 12In; For motor protection: 14In; For power distribution: 10In
Tripping time (s)<0.2
3.3 Circuit breaker protection characteristics
3.3.1 Inverse time limit breaking characteristics of distribution circuit breaker (see Table 4)Serial number1, 2
Test current nameNo tripping current is agreed, tripping current is agreed upon
Setting current multiple1.05In, 1.30In
Appointed time≥ 1h, <1h; ≥ 2h, <2h
Initial stateCold state, immediately following sequence number 1 Start after test
3.3.2 Inverse time limit breaking characteristics of circuit breaker for motor protection (see Table 5)Serial number1, 2
Test current nameNo tripping current is agreed, Agreed tripping current
Setting current multiple1.0In, 1.2In
Appointed time≥ 2h, <2h
Initial stateCold state, starting immediately after test number 1

Parameter table 2

Parameter classificationParameter itemParameter value
3.4 Shunt tripperRated control power supply voltageAC220V, AC380V.
When the rated control power supply voltage is between 70% and 110%, the shunt release should reliably trip the circuit breaker.
3.5 Undervoltage releaseRated working voltageAC220V, AC380V.
When the voltage drops (even slowly drops) to the range of 70%-35% of the rated voltage, the undervoltage release should operate. When it is lower than 35% of the rated voltage of the release, the undervoltage release should be able to prevent the circuit breaker from closing. When the power supply voltage is equal to or greater than 85%, it should be able to ensure that the circuit breaker is closed.
3.6 Alarm contact Rated working voltageAC220V, agreed heating current: 3A.
3.7 Auxiliary contactConnected I/le10
Connected U/Ue1
Connected cosΦ0.3
On T0.95ms1
Off I/le1
Off U/Ue1
Break cosΦ0.3
Break T0.956×Pe
Operating frequency (times/h)120
Power-on time (s)0.05-2
3.8 External accessories of circuit breakerModelDZ20Y-100, DZ20C-160, DZ20Y-225, DZ20Y-400, DZ20Y-630, DZ20Y-1250
Height H152.5, 164.5, 230, 245, 275
Structural formMotor
Voltage specificationAC50Hz, 220V, 380V
3.8.2 Manual operating mechanism installation dimensionsModelDZ20Y-100, DZ20C-160, DZ20Y-225, DZ20Y-400, DZ20Y-630
Installation dimensions H (mm)60, 60, 68, 75, 77
X value of the operating handle relative to the center of the circuit breaker0, 0, 0, 0, 0
Handle length L (mm)65, 95

Requirement confirmation

Application, rating, quantity and drawings are checked first.

Factory matching

Supplier capacity, certificates and production slot are reviewed.

Order transaction

Confirm commercial terms, sign the commercial contract, and confirm the related document checklist.

Shipment control

Packing photos, inspection records and delivery status are tracked.