| 3.1 Main technical parameters of the circuit breaker (see table 2) | Model | DZ20Y-100, DZ20C-160, DZ20Y-225, DZ20Y-400, DZ20Y-630, DZ20Y-1250 |
| Number of poles | 3P |
| Rated operating voltage Ue (V) | 400, 400, 400, 380, 380, 380 |
| Rated insulation voltage Ue (V) | 800 |
| Short circuit breaking capacity kA (effective value) Icu/cosΦ | 18/0.30, 12/0.30, 25/0.25, 30/0.25, 30/0.25, 50/0.25 |
| Short circuit breaking capacity kA (effective value) Ics/cosΦ | 14/0.30, 8/0.5, 19/0.30, 23/0.25, 23/0.25, 32.5/0.25 |
| Rated circuit breaker current In A | 32, 40, 50, 63, 80, 100; 100, 125, 160; 125, 160, 180, 200, 225; 250, 315, 350, 400; 500, 630; 800, 1000, 1250 |
| Number of operating cycles | With load: 1500, 1000, 1000, 1000, 1000, 500; No load: 8500, 7000, 7000, 4000, 4000, 2500 |
| Operation frequency / hour | 120, 120, 120, 60, 60, 20 |
| Arc distance mm | 50, 50, 50, 100, 100, 120 |
| 3.2 Circuit breaker short-circuit protection current setting value (see table 3) | Model number | DZ20Y-100, DZ20C-160, DZ20Y-225, DZ20Y-400, DZ20Y-630, DZ20Y-1250 |
| Instantaneous operating current setting value of distribution circuit breaker Ii(A) and tolerance | In ≤ 40A: 500, ±20%; In> 40A: 10In, ±20%; 10In, ±20%; 10In, ±20%; 10In, ±20%; 7In,±20% |
| Instantaneous operating current setting value Ii (A) and tolerance of circuit breaker for motor protection | In ≤ 40A: 600, ±20%; In>40A: 12In, ±20%; 12In, ±20%; 12In, ±20%; 12In,±20%; - |
| Single-pole short-circuit protection current action setting value Ii(A) | For power distribution: In ≤ 40A: 700; In > 40A: 14In; For motor protection: In ≤ 40A: 850; In > 40A: 17In; For power distribution: 14In; For motor protection: 16In; For power distribution: 12In; For motor protection: 14In; For power distribution: 10In |
| Tripping time (s) | <0.2 |
| 3.3 Circuit breaker protection characteristics | | |
| 3.3.1 Inverse time limit breaking characteristics of distribution circuit breaker (see Table 4) | Serial number | 1, 2 |
| Test current name | No tripping current is agreed, tripping current is agreed upon |
| Setting current multiple | 1.05In, 1.30In |
| Appointed time | ≥ 1h, <1h; ≥ 2h, <2h |
| Initial state | Cold state, immediately following sequence number 1 Start after test |
| 3.3.2 Inverse time limit breaking characteristics of circuit breaker for motor protection (see Table 5) | Serial number | 1, 2 |
| Test current name | No tripping current is agreed, Agreed tripping current |
| Setting current multiple | 1.0In, 1.2In |
| Appointed time | ≥ 2h, <2h |
| Initial state | Cold state, starting immediately after test number 1 |