| 4.1 Rating of circuit breaker (see Table 2) | Model | NM1B-125S |
| Frame rating rated current (A) | 125 |
| Rated current (A) | 10, 16, 20, 25, 32 , 40, 50, 63, 80, 100, 125 |
| Rated operating voltage Ue(V) | 400 |
| Rated insulation voltage Ui (V) | 800 |
| Rated ultimate short-circuit breaking capacity (kA) |
| Rated operating short-circuit breaking capacity (kA) | 15 |
| Machine Mechanical life (times) | 20000 |
| Electrical life AC400V (times) | 3000 |
| Number of poles | 3, 4 |
| Arc distance (mm) | ≤50 |
| Model number | NM1B-W125S |
| Frame rating rated current (A) | 125 |
| Rated current (A) | 63, 70, 75, 80, 90, 100, 110, 120, 125 |
| Rated operating voltage Ue(V) | 400 |
| Rated insulation voltage Ui(V) | 800 |
| Rated ultimate short-circuit breaking capacity (kA) | 35 |
| Rated operating short-circuit breaking capacity (kA) | 17.5 |
| Mechanical life (times) | 20000 |
| Electrical life AC400V (times) | 3000 |
| Number of poles | 3, 4 |
| Arc distance (mm) | ≤50 |
| Rated Working voltage Ue(V) | 690 |
| Rated insulation voltage Ui(V) | 800 |
| Rated ultimate short-circuit breaking capacity (kA) | 3 |
| Rated operating short-circuit breaking capacity (kA) | 3 |
| Model number | NM1B-160S |
| Frame grade Rated current (A) | 160 |
| Rated current (A) | 63, 80, 100, 125, 140, 150, 160 |
| Rated operating voltage Ue(V) | 400 |
| Rated insulation Voltage Ui (V) | 800 |
| Rated ultimate short-circuit breaking capacity (kA) | 35 |
| Rated operating short-circuit breaking capacity (kA) | 17.5 |
| Mechanical life (times) | 20000 |
| Electrical life AC400V (times) | 3000 |
| Number of poles | 3, 4 |
| Arc distance (mm) | ≤50 |
| Rated operating voltage Ue(V) | 690 |
| Rated insulation voltage Ui(V) | 800 |
| Rated ultimate short-circuit breaking capacity (kA) | 3 |
| Rated operating short-circuit breaking capacity (k A) | 3 |
| Model number | NM1B-250S |
| 250 |
| Rated current (A) | 160, 180, 200, 225, 250 |
| Rated operating voltage Ue(V) | 400 |
| Rated insulation Voltage Ui (V) | 800 |
| Rated limit short-circuit breaking capacity (kA) | 35 |
| Rated operating short-circuit breaking capacity (kA) | 17.5 |
| Mechanical life (times) | 20000 |
| Electrical life AC400V (times) | 3000 |
| Number of poles | 3, 4 |
| Arc distance (mm) | ≤50 |
| Rated operating voltage Ue(V) | 690 |
| Rated insulation voltage Ui(V) | 800 |
| Rated ultimate short-circuit breaking capacity (kA) | 4 |
| Rated operating short-circuit breaking capacity ( kA) | 4 |
| Model number | NM1B-400S |
| 400 |
| Rated current (A) | 250, 315, 400 |
| Rated operating voltage Ue(V) | 400 |
| Rated insulation voltage Ui(V) | 1000 |
| Rated ultimate short-circuit breaking capacity (kA) | 35 |
| < /td> | Rated operating short-circuit breaking capacity (kA) | 17.5 |
| Mechanical life (times) | 5000 |
| Electrical life AC400V (times) | 1000 |
| Number of poles | 3, 4 |
| Arc distance (mm) | ≤100 |
| 4.2 Distribution circuit breaker Inverse time limit breaking action characteristics when all poles of the current release are energized at the same time (see Table 3) | Serial number | 1 |
| Test current name | Agreed no tripping current |
| I/In | 1.05 |
| Appointed time | 2h (In>63A), 1h (In≤63A) |
| Initial state | Cold state |
| Serial number | 2 |
| Test current name | Conventional tripping current |
| I/In | 1.30 |
| Appointed time | 2h(I n>63A), 1h (In≤63A) |
| Initial state | Start immediately after test number 1 |
| Serial number | 1 |
| < /td> | I/In | 1.0 |
| Appointed time | >2h |
| Initial state | Cold state |
| Remarks | |
| Serial number | 2 |
| I/In | 1.2 |
| Appointed time | ≤2h |
| Initial state | Start immediately after test number 1 |
| Remarks | 10≤In≤25 |
| Serial number | 3 |
| I/In | 1.5 |
| Appointed time | ≤2min |
| Initial state | Hot state |
| Remarks | 30 |
| Appointed time | ≤8min |
| Initial state | Hot state |
| Serial number | 4 |
| I/In | 7.2 |
| Appointed time | 0.5s≤T≤5s |
| Initial status |
| Remarks | 10≤In≤25 |
| Appointed time | 6s≤T≤20s |
| Initial state | Cold state |
| Remarks | 30≤In≤400 |
| 4.4 Circuit breaker short-circuit protection current setting value (see Table 5) | Model | NM1B-1 25S |
| Instantaneous operating current setting value II (A) and tolerance of distribution circuit breaker | 10In,±20% |
| The instantaneous operating current setting value II (A) and tolerance of the circuit breaker for motor protection | 12In, ±20% |