Function and use
Chint NM5NELE series residual current action circuit breakers are suitable for AC 50/60Hz, rated voltage AC415V and below, and rated current 10A to 800A circuits. Its main function is to provide indirect contact protection against fatal personal electric shock, to provide protection against electrical fires caused by ground fault current, such as insulation damage, and to provide protection against overload, short circuit and under-voltage of the line, and can also be used for infrequent switching of lines.
Detailed description
Advantages/core functions:
01 Excellent performance
With AC type/A type leakage action protection characteristics
Can provide additional protection for DC pulsating leakage situations, such as charging piles, medical equipment, precision electronic equipment, etc.
Leakage current/delay time is adjustable in four levels, providing customers with a wider adjustment range and reducing replacement costs caused by capacity expansion
02 Flexible and easy to use
The entire series of products can achieve free top/bottom cable entry
Industry-leading miniaturized design of accessories, 4 types of accessories can be installed at the same time, meeting a variety of extended functional requirements
03 Easy to use
The accessories realize box-type modular installation, the accessory frame is streamlined, easy to maintain and replace, and reduces the inventory of spare parts/spare parts
Detailed parameters
Parameter table 1
< td>Q< /tr>
| Parameter classification | Parameter item | Parameter value |
|---|
| Product model | | NM5NELE-125 |
| System parameter | Rated operating current In(A),40℃ | 25-32-40-50-63-80-100-125 |
| Electrical performance | Rated insulation resistance Ui(V) | 1000 |
| Rated impulse withstand voltage Uimp(kV) | 8 |
| Rated operating voltage Ue(V),AC50/60Hz | 380/400/415 |
| Number of poles | 3P |
| | 4P(3P+N, 4P) |
| Breaking ability | F |
| |
| | R |
| Rated limit short circuit breaking capacity Icu(kA) | AC380/400/415V 36 |
| | 50 |
| | 70 |
| Rated operating short-circuit breaking capacity Ics(kA) | AC380/400/415V 36 |
| | 50 |
| | 50 |
| Communication indication | Power on indication | |
| Leakage Alarm does not trip | |
| Conforms to standards | IEC/EN60947-2GB/T14048 .2 |
| Usage category | A |
| Working environment temperature (℃) | ~-25~+70 |
| Isolation function | |
| Installation and connection | Wiring method | Up/down free entry and exit lines |
| Flashover distance | ≤ 50/Zero flashover (need to install short sub-hood TCY) |
| Mechanical life (times) | Maintenance-free 20000 |
| | With maintenance 40000 |
| Electrical life (times) | AC40/415V 10000 |
| Protection type | Distribution protection |
| | Motor protection |
| Fixed | Plate front connection |
| | Back panel connection |
| Plug-in type | Front connection |
| | Rear connection |
| Outline dimensions (mm) | Width (W)×Height (H)×Depth (D) | 3P 92×160×75.5 |
| | 92×160×91 |
| | 4P 122×160×75.5 |
| | 122×160×91 |
| Note | 1. The isolation function is not suitable for 4A/4D poles. type circuit breaker; | |
| 2. When wiring down the incoming line, the breaking capacity needs to be derated by 75%; | |
| 3. The applicable rated voltage range of the advanced controller is: 100VAC~415VAC; | |
| 4. The breaking capacity of the advanced controller is only Q type. | |
Parameter table 2
< td>
| Parameter classification | Parameter item | Parameter value |
|---|
| System parameter | Current range | 125-160- 180-200-225-250 |
| | 250-315-350-400 |
| Rated voltage | 1000 |
| | 1000 |
| Rated frequency | 8 |
| | 12 |
| Rated insulation voltage | 380/400/415 |
| | 380/400/415 |
| Wiring method | F Q R |
| | F Q R |
| Rated short-time withstand current | 36 50 70 |
| | 36 50 70 100 |
| Rated peak withstand current | 36 50 50 |
| | 50 70 70 |
| Standard | IEC/EN60947-2, GB/T14048.2 |
| Model | A |
| Temperature range | -25~+70 |
| Inlet method | Up / Lower free entry |
| Zero flashover | ≤50/zero flashover (need to install short-circuit sub-cover TCV) |
| Performance index | Rated limit short-circuit breaking capacity | 20000 |
| | 10000 |
| Rated operating short-circuit breaking capacity | 4000 0 |
| | 20000 |
| Rated connection capacity | 10000 |
| 8000 |
| Communication | | |
| Protection function | | |
| Installation | Dimensions | 107×175×76.5 |
| | 107×175×101.5 |
| | 140×267×111 |
| | 140×267×111 |
| | 142×175×76.5 |
| | 142×175×101.5 |
| | 184×267×111 |
| | 184×267×111 |
Parameter table 3
< td>
| Parameter classification | Parameter item | Parameter value |
|---|
| Product model | | NMSNELE-630 |
| Rated operating current In,40°C | | 400-500-630 |
| Electrical performance | Rated insulation voltage Ui(V) | 1000 |
| Rated impulse withstand voltage Uimp(kV) | 12 |
| Rated operating voltage Ue(V),AC50/60Hz | 380/400/415 |
| Number of poles | 3P |
| | 4P (3P+N, 4P) |
| Breaking capacity | F |
| | Q |
| | R |
| Rated limit short circuit breaking capacity Icu(kA) | AC380/400/415V 50 |
| | 70 |
| | 100 |
| Rated operating short-circuit breaking capacity Ics(kA) | AC380/400/415V 50 |
| | 70 |
| | 70 |
| Power-on indication | ■ |
| Leakage alarm does not work Trip | |
| Comply with standards | IEC/EN60947-2.Z/GB/T14048 .2 |
| Usage category | A |
| Working environment temperature (°C) | -25~+70 |
| Isolation function | ■ |
| Wiring method | Free entry and exit of upper/lower wires |
| Arc distance | ≤50/zero arcing (need to install short terminals CV) |
| Mechanical life (times) | Maintenance-free 10000 |
| | With maintenance 20000 |
| Electrical life (times) | AC400/415V 8000 |
| Protection type | Distribution protection |
| | Motor protection |
| Installation and connection | Fixed | Front plate connection ■ |
| | Back-board connection ■ |
| Plug-in type | Front-board connection ■ |
| | Back-board connection ■ |
| Dimensions | Width (W) × Height (H) × Depth (D) | 3P 140×267×111 140×267×111 |
| | 4P 184×267×111 184×267×111 |
| Note | 1. The isolation function is not applicable to circuit breakers with 4A/4D poles; Use; | |
| 3. The applicable rated voltage range of the advanced controller is 100VAC-415VAC; | |
| 4. The breaking capacity of the advanced controller is only Q type. | |
Parameter table 4
| Parameter classification | Parameter item | Parameter value |
| NMSNELE-800 | System parameters | 800:400-500-630-700-800 |
| | | 1000 |
| | 12 |
| | 380/400/415 |
| F | 50 |
| | Q | 70 |
| R | 100 |
| | 50 |
| | 70 |
| | 70 |
| 10000 | |
| 20 000 | |
| 800:5000 | |