Function and use
Chint NM5PLE series residual current action circuit breakers are suitable for AC 50/60Hz, rated voltage AC415V and below, and rated current 10A to 800A circuits. Its main function is to provide indirect contact protection against fatal personal electric shock, to provide protection against electrical fires caused by ground fault current, such as insulation damage, and to provide protection against overload, short circuit and under-voltage of the line. It can also be used for infrequent switching of lines.
Detailed description
Advantages/core functions:
01 Excellent performance
With AC type/A type leakage action protection characteristics
Can provide additional protection for DC pulsating leakage situations, such as charging piles, medical equipment, precision electronic equipment, etc.
Leakage current/delay time is adjustable in four levels, providing customers with a wider adjustment range and reducing replacement costs caused by capacity expansion
02 Flexible and easy to use
The entire series of products can achieve free top/bottom cable entry
Industry-leading miniaturized design of accessories, 4 types of accessories can be installed at the same time, meeting a variety of extended functional requirements
03 Easy to use
The accessories realize box-type modular installation, the accessory frame is streamlined, easy to maintain and replace, and reduces the inventory of spare parts/spare parts
Detailed parameters
Parameter table 1
td>
| Parameter classification | Parameter item | Parameter value |
|---|
| Product model | | NMSPLE-100 |
| Electrical performance | Rated operating current In(A),40℃ | 10-16-20-25-32-40-50-63-80-100 |
| Rated insulation voltage Ui(V) | 1000 |
| Rated impulse withstand voltage Uimp(kV) | 8 |
| Rated operating voltage Ue(V),AC50/60Hz | 380/400/415 |
| Number of poles | 3P |
| | 4P(3P+N, 4P) |
| Breaking capacity | F |
| | Q |
| Rated limit short circuit breaking capacity Icu(kA) | AC380/400/415V 25 |
| | AC380/400/415V 36 |
| Rated operating short-circuit breaking capacity Ics(kA) | AC380/400/415V 25 |
| | AC380/400/415V 36 |
| Power-on indication | ■ |
| Leakage alarm does not trip | ■ |
| Comply with standards | IEC/EN60947-2, GB/T14048.2 |
| Use category | A |
| Working ambient temperature (℃) | -25~+70 |
| Isolation function | ■ |
| Wiring method | Up / Free incoming and outgoing lines |
| Flashover distance | ≤ 50/zero flight (need to install short terminal TCV) |
| Installation and connection | Mechanical life (times) | Maintenance-free 20000 |
| | With maintenance 40000 |
| Electrical life (times) | AC400/415V 10000 |
| Protection type | Distribution protection ■ |
| | Motor protection ■ |
| Fixed | Plate front connection ■ |
| | Back-board connection ■ |
| Plug-in type | Front-board connection / |
| | Back-board connection / |
| Outline Dimensions | Outline Dimensions (mm) Width (W) × Height (H) × Depth (D) | 3P 75*155*68.5 |
| | 4P 100*155*68.5 |
| Note | 1. The isolation function is not suitable for circuit breakers with 4A/4D poles; | |
| 2. When wiring down the incoming line, the breaking capacity is reduced to 75%. Use; | |
| 3. The applicable rated voltage range of the advanced controller is 100VAC~415VAC; | |
| 4. The breaking capacity of the advanced controller is only Q type. | 25-32-40-50-63-80-100-125; NM5PLE-250: 125-160-180-200-225-250 |
| Rated voltage | 1000 |
| Rated current | 8 |
| Rated insulation voltage | 380/400/415 |
| Number of poles | F, Q, R |
| Rated short-circuit breaking capacity | 36, 50, 70 |
| Performance index | Rated short-time withstand current | 36, 50, 50 |
| Rated limited short-circuit current | 20000 |
| Rated peak withstand current | 40000 |
| Rated short-circuit making capacity | 10000 |
| Communication | | ■, , 122×160×75.5, 122×160×91; NM5PLE-250: 107×175×76.5, 107×175×101.5, 142×175×76.5, 142×175×101.5 |
Parameter table 3
| Parameter classification | Parameter item | Parameter value |
|---|
| Product model | | NM5PLE-400 |
| System parameter | Rated operating current In(A),40℃ | 250-315-350-400 |
| Electrical properties | Rated insulation voltage U(I)(V) | 1000 |
| Rated impulse withstand voltage Uimp(kV) | 12 |
| Rated operating voltage Ue(V), AC50/60Hz | 380/400/415 |
| Number of poles | 3P ■ ■ n ■ |
| | R ■ ■ ■ |
| Rated short-circuit breaking capacity Icu(kA) | AC380/400/415V 50 ■ ■ ■ |
| | 70 ■ ■ ■ |
| | 100 ■ ■ ■ |
| Rated operating short-circuit breaking capacity Ics(kA) | AC380/400/415V 50 ■ ■ ■ |
| | 70 ■ ■ ■ |
| | 70 ■ ■ ■ |
| Communication instructions | Electronic tuning alarm does not trip | ■ |
| Comply with standards | IEC/E N60947-2, GB/T14048.2 |
| Use category | A |
| Working environment temperature (℃) | +25~+70 |
| Protection function | Isolation function | ■ |
| Wiring method | Up / Lower free entry |
| Flashover distance | ≤ 50/zero flashover (need to install short terminal cover TCV) |
| Mechanical life | Maintenance-free (times) | 10000 |
| With maintenance (times) | 20000 |
| Electrical life | AC400/415V | 8000 |
| Installation and connection | Protection type | Distribution protection ■ |
| | Motor protection ■ |
| Fixed | Front connection ■ |
| | Rear connection ■ |
| Plug-in | Front connection ■ |
| | Rear connection ■ |
| Dimensions | Width (W) × Height (H) × Depth (D) | 3P 140×267×111 140×267×111 |
| | 4P 184×267×111 184×267×111 |
| Note | 1. The isolation function is not suitable for circuit breakers with 4A/4D poles; Use; | |
| 3. The applicable rated voltage range of the advanced controller is 100VAC~415VAC; | |
| 4. The breaking capacity of the advanced controller is only Q type. | |
Parameter table 4
| Parameter classification | Parameter item | Parameter value |
|---|
| System parameter | Rated voltage | 400-500-630 |
| Rated Current | 1000 |
| Rated frequency | 12 |
| Rated insulation voltage | 380/400/415 |
| Rated short circuit breaking capacity | F: 50, Q: 70, R: 100 |
| Rated short-time withstand current | 50, 70, 70 |
| Performance indicators | Rated peak withstand current | 10000 |
| Rated short-time withstand current | 200 00 |
| Rated short-circuit making current | 8000 |
| Rated short-circuit breaking current | 800-5000 W630:8000 |
| Communication | | |
| Protection function | | |
| Installation | Rated size | 140×267×111 |
| Rated weight | 184×267× 111 |
| Rated installation size | 182*280*115 |
| Rated installation weight | 240*280*115 |
| NMSPLE-800(W630) | Rated voltage | 800:400-500-630-700-800 W630:400-500-630 |
| Rated current | 1000 |
| Rated frequency | 12 |
| Rated insulation voltage | 380/400/415 |
| Rated short-circuit breaking capacity | F: 50, Q: 70, R: 100 |
| Rated short-time withstand current | 50, 70, 70 |
| Rated peak withstand current | 10000 |
| Rated short-time withstand current | 20000 |
| Rated short-circuit making current | 8000 |
| Rated short-circuit breaking current | 800-5000 W630:8000 |
| Rated size | 140×267×111 |
| Rated weight | 184×267×111 |
| Rated installation size | 182*280*115 |
| Rated installation weight | 240*280*115 |