Functional purpose
1 Comply with standard GB/T 14048.2/IEC 60947-2
Detailed description
Parameters:
Rated current (In): 1A, 2A, 3A, 4A, 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A
Rated operating voltage (Ue): 230V/400V
Rated insulation voltage (U): 500V
Frequency: 50/60HZ
Instant tripping characteristics: C, D
Number of poles: 1P, 2P, 3P, 4P
Mechanical life: 20000 times
Electrical life: 10,000 times
Rated short circuit breaking capacity (lcn): 6000A
Operating short circuit breaking capacity (lcs): 6000A
Rated impulse withstand voltage (Uimp): 4kV
Advantages/core functions:
01 Excellent performance
The breaking capacity can reach 6kA, ensuring the reliability of the circuit breaker's breaking and the stability of the user's electricity consumption
The built-in energy storage mechanism realizes rapid closing, improves closing synchronization and improves electrical life
02 Flexible and easy to use
Tool-free installation of accessories can easily expand a variety of functions
Red and green indicator windows, "red" closing and "green" opening, prompting the contact closed status, safe and visible
Detailed parameters
2540
| Parameter classification | Parameter item | Parameter value |
|---|
| Rated current | In: | 1A, 2A, 3A, 4A, 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A. |
| Rated operating voltage | Ue: | 230/400V. |
| Rated insulation voltage | Ui: | 500V. |
| Frequency | | 50/60Hz. |
| Instant tripping characteristics | Type C (8In-12In), Type D (11.4In-17In). | |
| Number of poles | | 1P, 2P, 3P, 4P. |
| Mechanical life | | 20,000 times. |
| Electrical life | | 10,000 times. |
| Rated short-circuit breaking capacity | Icn: | 6000A. |
| Operating short-circuit breaking capacity | Ics: | 6000A. |
| Rated impulse withstand voltage | Uimp: | 4kV. |
| Power consumption per pole of the circuit breaker | See Table 1. | |
| Rated current In(A) | Maximum power consumption per pole (W) |
| In≤10 | 3 |
| 10 | 3.5 |
| 16 | 4.5 |
| 6 |
| 32 | 7.5 |
| 9 |
| 50 | 13 |