Functions and Uses
The DZ47-60M plastic-enclosed circuit breaker is suitable for AC 50Hz, rated voltage up to 400V, and rated current not exceeding 63A distribution lines; it can also be used in DC voltage single-pole not exceeding 110V, two-pole not exceeding 220V, and rated DC current not exceeding 63A distribution lines. The circuit breaker serves as a short-circuit protection device in the distribution line and can be used for infrequent switching in normal conditions.
Detailed Parameters
Parameter Table 1
| Parameter Category | Parameter Item | Parameter Value |
|---|
| Rated Current (In) | 1A, 2A, 3A, 4A, 5A, 6A, 10A, 15A, 16A, 20A, 25A, 32A, 40A, 50A, 60A, 63A |
| Poles | AC 1P, 2P, 3P, 4P DC 1P, 2P |
| Rated Insulation Voltage (Ui) | 500V |
| Rated Impulse Withstand Voltage (Uimp) | 6kV |
| 4.1 Main Classification | | |
| 4.1.1 According to Instantaneous Trip Type (see Table 1) | Instantaneous Trip Type | Action Current Range |
| B | 3.2In<l≤4.8In |
| C | 6.4In<l≤9.6In |
| D | 9.6In<l≤14.4In |
| 4.2 Technical Parameters | | |
| 4.2.1 Rated Ultimate Short-Circuit Breaking Capacity (Icu) (see Table 2, Table 3). | | |
| 4.2.2 Mechanical and Electrical Life: a. Electrical Life: 4000 times; b. Mechanical Life: 10000 times. | | |
| Rated Current (A) | Poles Voltage (V) Rated Ultimate Short-Circuit Breaking Capacity Icu (A) Trip Type |
| 1~40 | 1 230 6000 B, C |
| | 2, 3, 4 400 |
| 50~63 | 1 230 4500 B, C |
| | 2, 3, 4 400 |
| 1~63 | 1 230 4500 D |
| | 2, 3, 4 400 |
Parameter Table 2
| Parameter Category | Parameter Item | Parameter Value |
|---|
| Rated Current (In) | 1A, 2A, 3A, 4A, 5A, 6A, 10A, 15A, 16A, 20A, 25A, 32A, 40A, 50A, 60A, 63A |
| Poles | AC: 1P, 2P, 3P, 4P DC: 1P, 2P |
| Rated Insulation Voltage (Ui) | 500V |
| Rated Impulse Withstand Voltage (Uimp) | 6kV |
| 4.1 Main Classification | | |
| 4.1.1 According to Instantaneous Trip Type (see Table 1) | Instantaneous Trip Type | Action Current Range |
| B | 3.2In<l≤4.8In |
| C | 6.4In<l≤9.6In |
| D | 9.6In<l≤14.4In |
| 4.2 Technical Parameters | | |
| 4.2.1 Rated Ultimate Short-Circuit Breaking Capacity (Icu) (see Table 2, Table 3). | | |
| 4.2.2 Mechanical and Electrical Life: a. Electrical Life: 4000 times; b. Mechanical Life: 10000 times. | | |
| Rated Current (A) | Poles Voltage (V) Rated Ultimate Short-Circuit Breaking Capacity Icu (A) Trip Type |
| 1~40 | 1 230 6000 B, C |
| | 2, 3, 4 400 |
| 50~63 | 1 230 4500 B, C |
| | 2, 3, 4 400 |
| 1~63 | 1 230 4500 D |
| | 2, 3, 4 400 |
Parameter Table 3
| Parameter Category | Parameter Item | Parameter Value |
|---|
| System Parameters | Rated Current (A) | 1~40, 50~63, 1~63 |
| Poles | 1, 2 |
| Voltage (V) | 110, 220 |
| Rated Ultimate Short-Circuit Breaking Capacity Icu (A) | 6000, 4500 |
| Trip Type | B, C, D |
| Performance Indicators | Instantaneous Trip Type | B, C, D |
| Test Current | 3.2In, 6.4In, 9.6In, 4.8In, 9.6In, 14.4In |
| Initial State | Cold State |
| Limit of Trip or No Trip Time | t ≤ 0.2s, t < 0.2s |
| Expected Result | No Trip, Trip |
| Notes | - |
| Installation | Tightening Torque of Terminal Block | 2.0N·m |
| Rated Cross-sectional Area of Copper Wire (mm²) | 1, 1.5, 2.5, 4, 6, 10, 16 |