NB5LE-63FB Residual Current Operated Circuit Breaker

Product category:
Residual Current Circuit Breaker (RCCB)
Product code:
P-324
Model:
NB5LE-63FB

Function & Use (Application Scenarios)

Final electrical equipment, residual current operated circuit breakers are mainly suitable for AC 50Hz, rated voltage 230V, 400V, rated current up to 63A circuits, to provide overload, short circuit and residual current protection, and can also be used as infrequent switching of the line under normal conditions.

Surprise on inquiry

Product highlights

  • Reliable overload protection
  • Short-circuit protection capability
  • Leakage protection support
  • Strong breaking capacity
  • Engineering Application Compatibility

Model

NB5LE-63FB

Main Product Parameters

CategorySwitchgearSecondary CategoryResidual current operated circuit breaker
ParametersRated working current: 6-63A; Rated breaking capacity: 6kA; Rated insulation voltage: 500V; Operating ambient temperature: -35°C~+70°C

Product details

Function and Usage

The NB5LE-63FB residual current operated circuit breaker is suitable for AC 50Hz, rated voltage 230V, 400V, and rated current up to 63A circuits, providing overload, short-circuit, and residual current protection. It can also be used for infrequent switching in normal conditions.

Detailed Description

Parameters:
Rated operating current: 6-63A
Rated breaking capacity: 6kA
Rated insulation voltage: 500V
Operating environmental temperature: -35°C~+70°C

Detail Parameters

Parameter CategoryParameter ItemParameter Value
System ParametersProduct ModelNB5LE-63FB
Rated Current In(A)6, 10, 16, 20, 25, 32, 40, 50, 63
Rated Voltage Ue(V)AC230(1P+N, 2P), AC400(3P, 3P+N, 4P)
Rated Frequency (Hz)50
Poles1P+N, 2P, 3P, 3P+N, 4P
Mechanical Life (Times)4000
Electrical Life (Times)4000
Rated Short Circuit Breaking Capacity Icn(A)6000
Running Short Circuit Breaking Capacity Isc(A)6000
Rated Insulation Voltage Ui(V)500
Rated Impact Withstand Voltage Uimp(kV)4
Rated Residual Current IΔn (mA)AC Type: 30, 50, 100, 300 A Type: 30, 100, 300
Residual Current Protection TypeAC Type, A Type
Tripping Mechanism Action TypeElectronic Type
Dielectric Test Voltage (V)2000(V50Hz, 1 minute)
Vibration Resistance (IEC/EN 6068-2-6)No significant vibration and impact places
Wiring TerminalMinimum Wire Cross-sectional Area (mm²)1
Maximum Wire Cross-sectional Area (mm²)25
Standard Connection Torque (N·m)2.0
Maximum Allowable Torque (N·m)2.5
Wire Insertion Depth (mm)13
Reference Temperature (℃)30
Operating Environmental Temperature (℃)+35~+70
Storage Environmental Temperature (℃)+35~-85
Applicable Altitude (m)≤2000
Tripping FormThermal-magnetic Tripping
Instantaneous Tripping TypeB Type (3ln~5ln) ■
C Type (5ln~10ln) ■
D Type (10ln~16ln) ■
Wiring MethodTop Entry
Installation MethodInstallation MethodTH35-7.5 Standard Rail
Pollution Degree2
Protection LevelIP20
Installed in Distribution BoxIP40
Removable AccessoriesRemovable AccessoriesAX-B5, AL-B5, SHT-B5, OVT-B5, UV-TB5, OUVT-B5

Requirement confirmation

Application, rating, quantity and drawings are checked first.

Factory matching

Supplier capacity, certificates and production slot are reviewed.

Order transaction

Confirm commercial terms, sign the commercial contract, and confirm the related document checklist.

Shipment control

Packing photos, inspection records and delivery status are tracked.