Function and Application
1. Complies with standard GB/T 16917.1, IEC 61009-1
Detailed Description
Parameters:
Rated Current (In): 6~40A
Rated Residual Operating Current (IΔn): 0.01A, 0.03A
Rated Operating Voltage (Ue): 230V~
Rated Insulation Voltage (Ui): 500V
Frequency: 50Hz
Instantaneous Tripping Characteristics: C, D
Poles: 1P+N
Mechanical Life: 20000 times
Electrical Life: 10000 times
Rated Short-Circuit Breaking Capacity (Icn): 4500A
Operational Short-Circuit Breaking Capacity (Ics): 4500A
Rated Impulse Withstand Voltage (Uimp): 4kV
Rated Residual Make-Break Capacity (IΔm): 500A
Advantages/Core Functions:
01 Long Service Life
Adopts a storage design to ensure fast contact closure, with a mechanical life of up to 20000 times and an electrical life of up to 4000 times, greatly reducing the cost of later maintenance and replacement.
02 Comprehensive Tripping Types
Features C and D type tripping, achieving more precise overcurrent protection level matching, meeting the needs of different scenarios and customers, significantly enhancing personal safety and equipment safety, and optimizing the selectivity of the distribution system.
03 Comprehensive Residual Current Specifications
The product has comprehensive residual current specifications, meeting the application needs of customers in different scenarios, greatly enhancing personal and equipment safety.
Detailed Parameters
| Parameter Category | Parameter Item | Parameter Value |
|---|
| Rated Current (In) | | 6A, 10A, 16A, 20A, 25A, 32A, 40A |
| Rated Residual Operating Current (IΔn) | | 0.01A, 0.03A |
| Rated Operating Voltage (Ue) | | 230V~ |
| Rated Insulation Voltage (Ui) | | 500V |
| Frequency | | 50Hz |
| Instantaneous Tripping Characteristics | | C, D |
| Poles | | 1P+N |
| Mechanical Life | | 20000 times |
| Electrical Life | | 10000 times |
| Rated Short-Circuit Breaking Capacity (Icn) | | 4500A |
| Operational Short-Circuit Breaking Capacity (Ics) | | 4500A |
| Rated Impulse Withstand Voltage (Uimp) | | 4kV |
| Rated Residual Make-Break Capacity (IΔm) | | 500A |
| Derating Factor for Parallel Installation of Multiple Units (Recommended Value) | ≤3 Units | (0.9~0.95)In |
| 4~6 Units | (0.80~0.86)In |
| 7~9 Units | (0.78~0.76)In |
| >9 Units | 0.76In |
| Rated Current Correction Factor for High Altitude Use (Recommended Value) | ≤2000m | In |
| 3000m | 0.96In |
| 4000m | 0.94In |
| 5000m | 0.92In |