NB8LE-63M residual current device

Product category:
Residual Current Circuit Breaker (RCCB)
Product code:
P-337
Model:
NB8LE-63M

Function & Use (Application Scenarios)

Final electrical appliances, residual current operated circuit breakers are mainly suitable for AC 50Hz, rated voltage 230V, rated current up to 63 in commercial office buildings, residential buildings, and general industrial applications of terminal distribution lines, providing overload, short-circuit protection, and leakage protection for the lines

Surprise on inquiry

Product highlights

  • Overload protection reliable
  • Short-circuit protection capability
  • Leakage current protection support
  • Engineering Application Compatibility
  • Stable and reliable operation

Model

NB8LE-63M

Main Product Parameters

CategorySwitchgearSecondary CategoryResidual current operated circuit breaker

Product details

Function and Usage

The NB8LE-63M residual current operated circuit breaker is mainly applicable to the terminal distribution lines of commercial office buildings, residential buildings, and general industrial applications with AC 50Hz, rated voltage 230V, and rated current up to 63. It provides overload, short-circuit protection, and leakage protection for the lines, and can also perform non-frequent switching operations under normal conditions.

Detailed Parameters

Parameter CategoryParameter ItemParameter Value
Product ModelNB8LE-63M
Rated Current (A)6, 10, 16, 20, 25, 32, 40, 50, 63
Rated Residual Operating Current (mA)General Type:0.01A, 0.03A, 0.05A, 0.075A, 0.1A, 0.3A
Delayed Type:0.05A, 0.075A, 0.1A, 0.3A
Leakage Protection TypeA Type, AC Type
Operation TypeGeneral Type, Delayed Type
Rated Voltage (V)230
Rated Frequency (Hz)50
Pole Number1P+N, 2P
Mechanical Life (Times)20000
Electrical Life (Times)10000
Rated Short Circuit Breaking Capacity (A)10000
Running Short Circuit Breaking Capacity (A)10000
Rated Insulation Voltage (V)500
Rated Impulse Withstand Voltage (1.2/50) (kV)4
Dielectric Test Voltage (V)(50Hz, 1 minute) 2000
Humidity and Heat Resistance (GB/T2423.4: 55°C/90~96%, 25°C/95~100%)28 Cycle Cycles
Vibration Resistance (IEC/EN60068-2-6)Places without significant vibration and impact
Wiring TerminalTerminal FormFrame Structure
Minimum Wire Cross-sectional Area (mm²)1
Maximum Wire Cross-sectional Area (mm²)25
Standard Connection Torque (N·m)2
Maximum Torsion (N·m)3.5
Wire Insertion Depth (mm)13
Reference Temperature (°C)30
Operating Environmental Temperature (°C)-35~+70
Storage Environmental Temperature (°C)-35~+85
Applicable Altitude (m)2000
Tripping FormThermal Magnetic Tripping
Electromagnetic Tripping TypeB Type (3In~5In)
C Type (5In~10In)
D Type (10In~16In)
Enclosure Flame Retardant GradeV0
Input MethodTop Input
Installation MethodTH35-7.5 Standard Rail
Pollution Level2
Protection LevelDirect InstallationIP20B
Installed in Distribution BoxIP40B
Removable AccessoriesS9, V9, XF9, XF9J, OVT-1, OUVT-1

Requirement confirmation

Application, rating, quantity and drawings are checked first.

Factory matching

Supplier capacity, certificates and production slot are reviewed.

Order transaction

Confirm commercial terms, sign the commercial contract, and confirm the related document checklist.

Shipment control

Packing photos, inspection records and delivery status are tracked.