NXBLE-63 Residual Current Operated Circuit Breaker

Product category:
Residual Current Circuit Breaker (RCCB)
Product code:
P-348
Model:

Function & Use (Application Scenarios)

Final electrical appliances, residual current operated circuit breakers products are mainly applicable to 1 in compliance with the standard GB/T16917.1, IEC61009-1, suitable for engineering matching, installation and maintenance, and long-term stable operation, meeting the on-site application needs of electrical systems.

Surprise on inquiry

Product highlights

  • Leakage protection support
  • Engineering Application Compatibility
  • Stable and reliable operation
  • Easy system integration

Model

Main Product Parameters

CategorySwitchgearSecondary CategoryResidual current operated circuit breaker

Product details

Function and Application

1. Complies with standard GB/T 16917.1, IEC 61009-1

Detailed Parameters

Parameter CategoryParameter ItemParameter Value
Rated Current (In)6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A.
Rated Residual Operating Current (IΔn)0.01A (1P+N, 2P), 0.03A, 0.05A, 0.075A, 0.1A, 0.3A (AC type); 0.03A, 0.1A, 0.3A (A type).
Rated Operating Voltage (Ue)230V~ (1P+N, 2P), 400V~ (3P, 3P+N, 4P).
Rated Insulation Voltage (Ui)500V.
Frequency50Hz.
Instantaneous Tripping CharacteristicsB, C, D.
Overvoltage Protection Range ValueSee Table 1.
Pole NumberSee Table 1.
Mechanical Life20000 times.
Electrical Life10000 times.
Breaking CapacitySee Table 1.
Rated Impulse Withstand Voltage (Uimp)4kV.
Rated Residual Make and Break Capacity (IΔm)630A.
Suggested Values for Product Application ScenariosFor reference only; the specific corrected value should be comprehensively evaluated based on the user's actual operating conditions.
Table 1
Product ModelPole NumberBreaking Capacity (A) Overvoltage Action Range
Icn Ics
NXBLE-63 (with A type)1P+N, 2P, 3P, 3P+N, 4P6000 6000 -
NXBLG-63 (without A type)1P+N, 2P6000 6000 (280±14)V
NXBLE-63H (with A type)2P10000 7500 -
Table 2
Product ModelNXBLE-63
Derating Factor for Parallel Installation of Multiple Units (Recommended Value)≤3 units(0.9–0.95)In
4–6 units(0.80–0.86)In
7–9 units(0.76–0.78)In
>9 units0.76In
Derating Factor for High Altitude Usage (Recommended Value)≤2000mIn
3000m0.96In
4000m0.94In
5000m0.92In

Requirement confirmation

Application, rating, quantity and drawings are checked first.

Factory matching

Supplier capacity, certificates and production slot are reviewed.

Order transaction

Confirm commercial terms, sign the commercial contract, and confirm the related document checklist.

Shipment control

Packing photos, inspection records and delivery status are tracked.