NB1LE-63 Residual Current Operated Circuit Breaker

Product category:
Residual Current Circuit Breaker (RCCB)
Product code:
P-356
Model:
NB1LE-63

Function & Use (Application Scenarios)

Final electrical appliances, residual current operated circuit breakers are mainly applicable to AC 50Hz, rated voltage single-pole two-wire, two-pole 230V, three-pole, three-pole four-wire, four-pole 400V, with rated current up to 63A in the circuit. When a person is electrocuted or the grid leakage current exceeds the specified value,

Surprise on inquiry

Product highlights

  • Reliable overload protection
  • Short-circuit protection capability
  • Leakage protection support
  • Engineering Application Compatibility
  • Stable and reliable operation

Model

NB1LE-63

Main Product Parameters

CategorySwitchgearSecondary CategoryResidual current operated circuit breaker

Product details

Function and Application

NB1LE-63 □ residual current device is suitable for AC 50Hz, rated voltage single-pole two-wire, two-pole 230V, three-pole, three-pole four-wire, four-pole 400V, rated current up to 63A circuits. When a person is electrocuted or the grid leakage current exceeds the specified value, the residual current device can automatically cut off the power supply within a very short time to ensure personal safety and prevent accidents caused by leakage current in equipment. The residual current device also has overload and short-circuit protection functions, which can be used to protect against circuit overloads and short circuits, and can also be used for non-frequent switching of circuits under normal conditions. Conforms to the standard: GB/T 16917.1, IEC 61009-1, and has obtained CCC certification.

Detailed Parameters

Parameter CategoryParameter ItemParameter Value
System ParametersRated Voltage (UC)AC 230V (1P+N, 2P), AC 400V (3P, 3P+N, 4P)
Rated Current (In)50A, 63A
Rated Limiting Short-Circuit Current (Icu)50kA
Rated Limiting Short-Circuit Closing Capacity (Icm)4kA
Rated Limiting Short-Circuit Breaking Capacity (Icn)0.03
Rated Limiting Short-Circuit Closing Capacity (Inm)0.05kA
Residual Current Protection FunctionAC Type
Poles1P+N, 2P, 3P, 3P+N, 4P
Residual Current Tripping FormC Type
Rated Residual Current Breaking Capacity (In)6300A (NB1L-E63), 10000A (NB1L-E63H)
Rated Limiting Short-Circuit Closing Capacity (Inm)500A (n=50A); 630A (n=63A)
Overcurrent Protection CharacteristicsConforms to 3, Figure 1
Mechanical and Electrical LifeConforms to 4
Wiring ConductorsTotal 5
Wiring Torque2.0N·m
Dimensions and Installation DimensionsSee Figure 2, Figure 3
Installation Method2 positions
Protection LevelIP20
Installation CategoryCategory III
Performance Indicators
Residual Current Operation Time
In(A)IΔn(mA)
50, 630.03
0.1
0.05
0.04
0.04
0.04
Residual Current Device Residual Current Characteristics (Reference Temperature 30℃)
Serial NumberRated Current (In) Start State Test Current Specified Time Expected Result Notes
a50, 63 Cold State 1.13In t≤1s No Trip
b50, 63 Immediately after test a 1.45In t≤1s Trip
c50, 63 Cold State 2.5In 1s≤t≤120s Trip
d50, 63 Cold State 10In t≤0.5s No Trip
Tripping Characteristic Curve

Requirement confirmation

Application, rating, quantity and drawings are checked first.

Factory matching

Supplier capacity, certificates and production slot are reviewed.

Order transaction

Confirm commercial terms, sign the commercial contract, and confirm the related document checklist.

Shipment control

Packing photos, inspection records and delivery status are tracked.