The NXCC series switching capacitor contactor (hereinafter referred to as the contactor) is mainly used in AC 50Hz (or 60Hz), rated working voltage up to 690V power lines, for the purpose of connecting or disconnecting low-voltage parallel capacitors in low-voltage reactive power compensation equipment. The contactor is equipped with a current surging suppression device, which can effectively reduce the closing surge current impact on the capacitor and suppress overvoltage during disconnection. It conforms to the standards: GB/T 14048.4, IEC/EN 60947-4-1.
Detailed Description
Parameters:
Rated Operating Current: (19~136.8)A
Capacitor Capacity Controllable: (7.2~156.3)kvar
Limit Working Temperature: -35°C~+70°C
Current Surging Suppression Capability: 20Ie
Advantages/Core Functions:
01 Excellent Performance, Easy Selection
Rated operating current increased by 5%~35%, capacitor capacity increased
02 Intelligent Manufacturing, Safe and Reliable
Full life cycle production and management system, automated testing for key processes
The product uses high-performance flame-retardant materials, the coil uses 180-class enamel wire, and the limit working temperature is -35°C~+70°C.
03 Flexible and Easy to Use, Convenient Installation
Increased number of auxiliary contacts, standard 3 pairs~5 pairs
The coil has A1, A2 terminals on both top and bottom for convenient wiring, meeting various wiring scenarios.
Detailed Parameters
| Parameter Category | Parameter Item | Parameter Value |
|---|
| NXCC-25 | 25 |
| NXCC-32 | 32 |
| NXCC-43 | 43 |
| NXCC-63 | 63 |
| NXCC-95 | 95 |
| NXCC-115 | 115 |
| NXCC-150 | 150 |
| NXCC-170 | 170 |
| Agreed Heating Current Ith(A) | Rated Current le(AC-6b)(A) | 19 |
| | 30.4 |
| | 39.4 |
| | 52.5 |
| | 91.9 |
| | 105 |
| | 121.6 |
| | 136.8 |
| Capacitor Capacity Controllable(kvar) | 220/230V | 7.2 |
| | 11.5 |
| | 15 |
| | 20 |
| | 35 |
| | 40 |
| | 46.3 |
| | 52.1 |
| 380/400V | 12.5 |
| | 20 |
| | 25.9 |
| | 34.5 |
| | 60.4 |
| | 69.1 |
| | 80 |
| | 90 |
| 660/690V | 21.7 |
| | 34.7 |
| | 45 |
| | 60 |
| | 105 |
| | 120 |
| | 139 |
| | 156.3 |
| Rated Insulation Voltage(V) | | 690 |
| Current Surging Suppression Capability | | 20le |
| Action Conditions | Engagement (85%-110%) Us; Release: (20%-75%) Us | |
| Circuit Power(VA) | Start/Keep | 70/9.5 |
| | 70/11.4 |
| | 70/11.4 |
| | 210/36.6 |
| | 300/36.6 |
| | 300/36.6 |
| | 1000/91.2 |
| | 1000/91.2 |
| Auxiliary Contact Control Capacity | AC-15: Ue/le: AC220V/230V/2.7A, AC380V/400V/1.5A; DC-13: Ue/le: DC220V/0.3A; Ith:10A | |
| Rated Impulse Withstand Voltage(Uimp) | | 6kV |
| Protection Level | | IP20 (applies only to the front side) |
| | IP10 |
| Coil Rated Control Power Supply Voltage Us(50Hz) | | 110V, 127V, 220V, 380V, 450V (other voltages and frequencies should be specified when ordering) |