Function and Use
The NC11 contactor is mainly used in electricity meter boxes to control the power supply system of the meter: Under normal conditions, the main contacts of the contactor are kept closed (i.e., the main contacts are four-pole normally closed, one of which is used for the user's protective neutral shorting). Only when the user has an arrears, the power supply department can send a signal to the contactor to energize the coil, thereby cutting off the power supply. It can also be used in distribution cabinets of cold storage rooms, laundries, etc.
Detailed Description
Parameters:
Rated Working Current: 65A
Rated Insulation Voltage: 690V
Number of Poles: 4P
Detail Parameters
| Parameter Category | Parameter Item | Parameter Value |
|---|
| Technical Parameter Indexes | Product Model and Specification | NC11-65/04 |
| Rated Insulation Voltage Ui | 690V |
| Rated Impulse Withstand Voltage Uimp | 8kV |
| Number of Poles | 4P |
| Ambient Temperature | Storage: -25℃~+55℃ Operation: -5℃~+40℃ |
| Maximum Operating Altitude | 2000m |
| Installation Method | Allowing an angle of ±5° from the normal vertical installation plane |
| Rated Working Current (Ue ≤ 440V) | AC-3: 65A AC-1: 80A |
| Rated Working Voltage | 400V |
| Agreed Free Air Heating Current Ith | 80A |
| Controlled Three-phase Squirrel Cage Motor Power kW | 230V: 18.5 400V: 30 |
| Mechanical Life (times) | 100 |
| Electrical Life (AC-3)(times) | 60 |
| Hot-state Pickup Voltage (+55℃) | (85%-110%)Us |
| Cold-state Release Voltage (-25℃) | (75%-20%)Us |
| Connection Wires | Soft Wire Without Terminals | 1 wire Minimum/Maximum mm²: 6/25 2 wires Minimum/Maximum mm²: 4/10 |
| Soft Wire With Terminals | 1 wire Minimum/Maximum mm²: 6/25 2 wires Minimum/Maximum mm²: 4/10 |
| Hard Wire Without Terminals | 1 wire Minimum/Maximum mm²: 6/25 2 wires Minimum/Maximum mm²: 4/10 |
| Tightening Torque | Main Circuit | 6 N.m |
| Control Circuit | 0.8 N.m |
| Selected Fuse Model | gG80 |
| Installation Category | Category III |
| Protection Level | IP10 |
| Pollution Degree | Level 3 |
| Auxiliary Contacts | The body does not come with auxiliary contacts, but each side can have one NCF1-11C attached |
| Contactors Applicable Working System | Eight-hour, continuous, intermittent cycle working system |
| Rated Coil Operating Voltage | AC110V, AC220V, AC380V |