| System Parameters | Maximum Rated Current I<sub>max</sub>(A) | 12, 32, 45 |
| Rated Operating Voltage U<sub>e</sub>/V(50Hz) | AC-43, AC-44 |
| Rated Running Short-Circuit Breaking Capacity I<sub>cs</sub>(kA) | 0.63-12, 4.5-32, 11.3-45 |
| Lifetime (ten thousand times) | 50, 4, 150, 120, 45 |
| Agreed Heating Current I<sub>th</sub>(A) | 12, 32, 45 |
| Rated Insulation Voltage U<sub>i</sub>(V) | 690 |
| Rated Impulse Withstand Voltage U<sub>imp</sub>(kV) | 6 |
| Poles | 3 |
| Control and Protection Module Parameters | Control and Protection Module Code | CTU-1 □ 0.63 □, CTU-1 □ 14 □, CTU-1 □ 5 □□, CTU-1 □ 12 □, CTU-1 □ 18 □, CTU-1 □ 32 □, CTU-1 □ 45 □ |
| Rated Current I<sub>r</sub>(A) | 0.63, 1.4, 5, 12, 18, 32, 45 |
| Overload Protection Setting Current I<sub>r</sub>(A) | 0.16-0.63, 0.35-1.4, 1.25-5, 3-12, 4.5-18, 8-32, 11.3-45 |
| Motor Power for Control at 400V/AC-43(kW) | 0.06-0.18, 0.09-0.55, 0.37-2.2, 1.1-5.5, 1.5-7.5, 3-15, 4-22 |
| Complementary Power Module (Main Body) | PBU-112, PBU-132, PBU-145 |
| Control Method | When A1, A2 is connected to the control power supply, the NK8 can be controlled by the operating handle to close/open. When the handle is rotated to OFF position, NK8 opens. When the handle is rotated to AUTO position, NK8 connects. | - |
| Protection Function | Short Circuit Instantaneous | 16le, 16le, 16le |
| Time-Current Overload | 12Ir, 6Ir-12Ir adjustable (default 12Ir+OFF T=0.2s), 3Ir-12Ir adjustable (default 12Ir+OFF) |
| Overload Inverse Time | √, -, √ |
| Phase Failure | - Three-phase current imbalance and action time factory set at 50% action time 1s |
| Tripping Level | 10A, 10E, 20E, 30E (default 10A), 10A, 5E, 10A, 10E, 15, 20E, 25, 30E (default 5E) |
| Residual Current | 20%le 1s, Fault protection current 20%-50% (default 20%) adjustable + OFF, Fault protection 110%-600% (default 600%) adjustable fault warning 110%-600% rated current (default 500%) adjustable fault protection delay 0.1s-20s (default 5s) adjustable + OFF |
| Locked Rotor | - Fault protection 5Ir-9Ir (default 5Ir) adjustable + OFF Fault protection delay 1s-15s (default 2s) adjustable Fault protection 110%-600% (default 250%) adjustable Fault warning 110%-600% (default 500%) adjustable Fault protection delay 0.1s-20s (default 5s) adjustable + OFF |
| Blockage | - Fault protection 5Ir-9Ir (default 5Ir) adjustable + OFF Fault protection delay 1s-15s (default 2s) adjustable Fault protection 110%-600% (default 250%) adjustable Fault warning 110%-600% (default 500%) adjustable Fault protection delay 0.1s-20s (default 5s) adjustable + OFF |
| Start Timeout | - Delay time 1s-60s (default 3s) adjustable Start time 0s-20s (default 10s) adjustable |
| Undervoltage | - Fault protection 20%-80% (default 80%) adjustable + OFF Fault protection delay 1s-60s (default 10s) adjustable Fault protection 20%-90% (default 50%) adjustable Fault warning 20%-90% (default 70%) adjustable Fault protection delay 0.1s-600s (default 5s) adjustable + OFF |
| Overvoltage | - Fault protection 70%-90% (default 80%) adjustable + OFF Fault protection delay 1s-30s (default 10s) adjustable Fault protection 110%-130% (default 110%) adjustable + OFF Fault protection delay 1s-30s (default 10s) adjustable |
| Measurement Function | Three-phase Current | - √ √ |
| Average Current | - √ √ |
| Grounding Current | - √ √ |
| Control Voltage | - - √ |
| Thermal Capacity | - - √ |
| Current Unbalance Rate | - - √ |