NKB8-63 Series Control and Protection Switchgear

Product category:
Control and Protective Switching Device (CPS)
Product code:
P-437
Model:
NKB8-63

Function & Use (Application Scenarios)

Motor control and protection devices, control and protection switchgear products are mainly applicable to (hereinafter referred to as "switch" or CPS), and are mainly applied to low-voltage power distribution and motor control and protection circuits with AC 50Hz, rated working voltage 690V and below, and rated working current 1.2A~63A

Surprise on inquiry

Product highlights

  • Overload protection reliable
  • Short-circuit protection capability
  • Strong breaking capacity
  • Control response is stable
  • Engineering Application Compatibility

Model

NKB8-63

Main Product Parameters

CategoryRelay Protection and Automation DevicesSecondary CategoryControl and Protection Switchgear
ParametersCurrent frame: 63; Rated operating voltage: ≤690V; Rated operating current: 0.15~63AAdvantages/Core Features01 Compact structure and reliable functions; 02 Has circuit overload and short circuit protection capabilities; 03 High breaking capacity

Product details

Function and Application

The NKB8-63 series of control and protection switchgear (hereinafter referred to as "switch" or CPS) is mainly applied in low-voltage distribution and motor control and protection circuits with AC 50Hz, rated operating voltage up to 690V, and rated operating current from 1.2A to 63A.

Detailed Description

Parameters:
Current housing: 63
Rated operating voltage: ≤690V
Rated operating current: 0.15~63A

Advantages/Core Functions:
01 Compact structure, reliable functions
02 Capable of overload and short-circuit protection of the circuit
03 High breaking capacity

Detail Parameters

Parameter CategoryParameter ItemParameter Value
4 Technical ParametersFrame Rating63
Rated Operating Voltage Ue400V, 690V
Usage CategoryAC-43, AC-44
Agreed Heating Current Ith(A)12 32 63
Rated Operating Current Ie(A)1.2, 2.4, 6, 12 18, 32 45, 63
Rated Frequency50Hz
Pole Number3
Rated Working SystemEight-hour working system, continuous working system, intermittent working system
Intermittent working system level 600, load factor 40%
Rated Short-Circuit Breaking Capacity Ics50kA(AC400V), 4kA(AC690V)
Breaking Action Time≤ 2ms
Rated Insulation Voltage Ui690V
Rated Impulse Withstand Voltage Uimp6kV
Electrical Life (AC—A33, ten thousand times)100(AC400V)
Mechanical Life (ten thousand times)1000
Table 2 Main Technical Parameters (Rated Current and Control Power)Rated Operating Current Ie(A)
Overload Setting Current Range Ir(A)
Controlled Motor Power Pe(kW)400VAC 690VAC
1.20.3-1.2 0.07-0.5 0.13-0.86
2.40.6-2.4 0.15-1.0 0.25-1.8
61.5-6 0.52-2.8 0.9-5.0
123-12 1.1-6.0 2.0-10
187.2-18 3.0-9.5 5.0-16
3212-32 5.0-16.5 8.5-29
4518-45 7.1-23.5 14-43
6325-63 10-35 19-60
Table 3 Main Technical Parameters (Control and Auxiliary Circuit)Rated Control Power Supply Voltage Us230VAC/50Hz
Auxiliary Switch Circuit2NO+2NC
Control Power Supply Voltage Us:DC-13, 110V/0.55A, 24V/5A
Auxiliary Signal Circuit2NO+1NC
Alarm Signal Circuit230VAC
Communication Module Circuit1NO
Maximum Coil Power:4VA
24VDC

Requirement confirmation

Application, rating, quantity and drawings are checked first.

Factory matching

Supplier capacity, certificates and production slot are reviewed.

Order transaction

Confirm commercial terms, sign the commercial contract, and confirm the related document checklist.

Shipment control

Packing photos, inspection records and delivery status are tracked.