| 4.1 Rated Control Power Supply Voltage of the Product | AC110V~AC240V, 50Hz/60Hz; DC110V~DC350V | Main Circuit: Rated Insulation Voltage AC690V, Rated Frequency 50Hz, Rated Impulse Withstand Voltage 1.2/50µs, 4kV |
| Rated Short-Circuit Current Limit (KA) | 125 |
| Rated Insulation Voltage UI V | AC690 |
| 4.2 Basic Parameters of the Auxiliary Circuit | Contact Number | 3 Normally Open Contacts, 1 Normally Closed Contact |
| Rated Thermal Current Ith A | AC-15: 1.5, ACa15: 0.47, DC13: 1 |
| Usage Category | AC240, AC415, DC30 |
| Rated Operating Voltage Ue V | AC240, AC415, DC30 |
| Rated Operating Current Ie A | AC240: 1.5, AC415: 0.47, DC30: 1 |
| Rated Insulation Voltage UI V | AC415, DC30 |
| Rated Impulse Withstand Voltage Uimp (1.2/50 µs) kV | 2.5 |
| 4.3 Product Functions are shown in Table 3. | Basic Protection Functions | Inverse Time Overload Protection, Thermal Memory Function, Underload Protection, Locked Rotor Protection, Blockage Protection |
| Extended Protection Functions | Timed Overload, Short Circuit, Phase Failure, Current Unbalance, Over Power, Under Power, Current Overflow, Phase Sequence, Overvoltage, Undervoltage, Start-up Timeout, Start-up Overfrequency, External Fault, Leakage, Grounding |
| Parameter Measurement | Three-phase Current, Three-phase Voltage, Demand/Earthing, Power, Energy Metering |
| Other Functions | RTC Clock, Event Recording, RS485 Communication, 6DI, 4DO DO |
| 4.4 Structural Features | | The main unit uses a panel-mounted installation method, and the current transformer uses a rail-mounted or assembled installation method. Plug-in terminal blocks facilitate user wiring. Multiple current specifications are available to meet different power motors. It has a programmable 4mA~20mA analog output function. Multiple DO outputs facilitate complex motor control. |
| 4.4.1 Set all protection parameters using the buttons. | | |
| 4.4.2 TFT LCD screen displays three-phase current, voltage, power true etc. electrical parameters and fault related information. | | |
| 4.4.3 LED light indicates the working status of the protector (start, operation, stop, fault). | | |
| 4.4.4 Supports button, DI input, and communication control for motor start and stop simultaneously. | | |
| 4.4.5 Current transformers use a rail-mounted or assembled installation method. | | |
| 4.4.6 Plug-in terminal blocks, convenient for user wiring. | | |
| 4.4.7 Multiple current specifications are available to meet different power motors. | | |
| 4.4.8 It has a programmable 4mA~20mA analog output function. | | |
| 4.4.9 Multiple DO outputs facilitate complex motor control. | | |