Function and Purpose
The JS11S series time relay is suitable for AC 50Hz, rated control circuit power supply voltage up to 380V or DC rated control circuit power supply voltage up to 24OV in the control circuit as a time control element, to connect or disconnect the circuit according to the predetermined time.
Detailed Parameters
| Parameter Category | Parameter Item | Parameter Value |
|---|
| Operation Mode | Power-on Delay | |
| Number of Contacts | 2 changeover contacts with delay, 1 changeover contact without delay |
| Contact Capacity | Ue/le: AC-15 240V/0.75A, 415V/0.47A; DC-13 220V/0.27A; Ith: 5A |
| Rated Control Circuit Power Supply Voltage | AC/DC 24V~48V, AC/DC 100V~240V, AC 220V, AC 380V, 50Hz |
| Permissible Fluctuation Range of Rated Control Circuit Power Supply Voltage | 85%-110% |
| Electrical Life | 1×10⁵ |
| Mechanical Life | 1×10⁶ |
| Delay Accuracy | ≤1% |
| Environmental Temperature | -5℃~+40℃ |
| Power Consumption | ≤3VA |
| Installation Method | Panel Mount |
| Model | JS11S | Delay: 0.01~9.99s, 0.1s~99.9s, 1s~999s, 0.1min~99.9min, 1min~999min, 0.1h~99.9h, 1h~999h, 1h~9999h, 1s~999min, 1min~9999.9min, 0.1min~999.9min, 1min~9999min, 0.1h~999.9h, 1h~9999h, 1s~9999min, 1min~9999h9min |
| JS11S-A | Delay: 0.01s~99.9s, 1s~99min99s, 1min~99h99min |