TNSZ3 Series AC Automatic Voltage Stabilizer

Product category:
Voltage Stabilizer
Product code:
P-616
Model:
TNSZ3

Function & Use (Application Scenarios)

Power electrical appliances and voltage stabilizers are mainly applicable to low-voltage power grids with a voltage level of 500V and below, and a rated frequency of 50Hz. They are suitable for various scenarios requiring voltage stabilization in industries, agriculture, construction, transportation, buildings, lasers, and other fields, and can be used for numerical control processing

Surprise on inquiry

Product highlights

  • Engineering Application Compatibility
  • Stable and reliable operation
  • Easy system integration

Model

TNSZ3

Main Product Parameters

CategoryPower Quality Monitoring and Treatment DeviceSecondary CategoryVoltage Regulator

Product details

Function and Usage

The TNSZ3 series column-type AC automatic voltage stabilizer is mainly used in low-voltage power grids with a voltage level of 500V and below, and a rated frequency of 50Hz. It is suitable for various applications requiring voltage stabilization in industries, agriculture, construction, transportation, buildings, lasers, etc., and can provide high-quality power supply for numerical control processing equipment, laser equipment, production lines, elevators, building distribution, air conditioning, and other loads.

Detailed Parameters

Parameter CategoryParameter ItemParameter Value
System ParametersItemTNSZ3-30
TNSZ3-50
TNSZ3-75
TNSZ3-100
Rated Capacity30kVA
50kVA
75kVA
100kVA
Rated Output Current46A
76A
114A
152A
Phase NumberThree-phase
Input Voltage Range304V~456V
Rated Output Voltage380V
Frequency50Hz
Voltage Stabilization Accuracy±1%~±5%
Protection FunctionsOvervoltage Protection Value at Output Terminal(418±3.8)V
Undervoltage Protection Value at Output Terminal(342±3.8)V
Overvoltage and Undervoltage Protection at Input TerminalAction Time ≤15 min
Overcurrent ProtectionAction Time <5 min when ≥1.2 times the rated output current

Requirement confirmation

Application, rating, quantity and drawings are checked first.

Factory matching

Supplier capacity, certificates and production slot are reviewed.

Order transaction

Confirm commercial terms, sign the commercial contract, and confirm the related document checklist.

Shipment control

Packing photos, inspection records and delivery status are tracked.