JJ1 Series Auto-Transformer Voltage Reduction Starting Control Cabinet

Product category:
soft starter
Product code:
P-422
Model:
JJ1

Function & Use (Application Scenarios)

Electric motor control and protection devices, electric motor starters are mainly applicable for infrequent reduced voltage starting of three-phase squirrel cage induction motors with AC 50Hz, rated voltage 380V, and rated output power of 400kW and below. They can manually disconnect the power circuit of the motor (not suitable for use

Surprise on inquiry

Product highlights

  • Strong breaking capacity
  • Control response is stable
  • Engineering Application Compatibility
  • Stable and reliable operation
  • Easy system integration

Model

JJ1

Main Product Parameters

CategoryInverters and Soft StartersSecondary categorySoft starter

Product details

Function and Usage

The JJ1 series auto-transformer voltage reduction starting control cabinet is suitable for three-phase squirrel cage induction motors with an AC frequency of 50Hz, rated voltage of 380V, and rated output power of 400kW and below for infrequent voltage reduction starting. It can manually disconnect the motor's power circuit (not used for the jogging, reverse connection braking, or reversing of squirrel cage induction motors, nor for circuits that frequently switch on and off or suddenly reverse the motor). Conforms to the standard: GB/T14048.4.

Detail Parameters

Parameter CategoryParameter ItemParameter Value
4 Main Technical ParametersModelJJ1-11
Control Motor Power (kW)11
Rated Operating Current (A)22
Current Transformer Current Ratio (A)50/5
Motor Protector or Thermal Overload Relay Setting Current Reference Value (A)22
Current - Time Conversion Device Setting Value (A)3.1
ModelJJ1-15
Control Motor Power (kW)15
Rated Operating Current (A)29
Current Transformer Current Ratio (A)50/5
Motor Protector or Thermal Overload Relay Setting Current Reference Value (A)29
Current - Time Conversion Device Setting Value (A)4.2
ModelJJ1-18.5
Control Motor Power (kW)18.5
Rated Operating Current (A)36
Current Transformer Current Ratio (A)50/5
Motor Protector or Thermal Overload Relay Setting Current Reference Value (A)36
Current - Time Conversion Device Setting Value (A)5.2
ModelJJ1-22
Control Motor Power (kW)22
Rated Operating Current (A)42
Current Transformer Current Ratio (A)75/5
Motor Protector or Thermal Overload Relay Setting Current Reference Value (A)42
Current - Time Conversion Device Setting Value (A)4.2
ModelJJ1-30
Control Motor Power (kW)30
Rated Operating Current (A)57
Current Transformer Current Ratio (A)75/5
Motor Protector or Thermal Overload Relay Setting Current Reference Value (A)57
Current - Time Conversion Device Setting Value (A)5.2
ModelJJ1-37
Control Motor Power (kW)37
Rated Operating Current (A)70
Current Transformer Current Ratio (A)100/5
Motor Protector or Thermal Overload Relay Setting Current Reference Value (A)70
Current - Time Conversion Device Setting Value (A)5.2
ModelJJ1-45
Control Motor Power (kW)45
Rated Operating Current (A)84
Current Transformer Current Ratio (A)100/5
Motor Protector or Thermal Overload Relay Setting Current Reference Value (A)84
Current - Time Conversion Device Setting Value (A)6.3
ModelJJ1-55
Control Motor Power (kW)55
Rated Operating Current (A)103
Current Transformer Current Ratio (A)200/5
Motor Protector or Thermal Overload Relay Setting Current Reference Value (A)103
Current - Time Conversion Device Setting Value (A)3.8
ModelJJ1-75
Control Motor Power (kW)75
Rated Operating Current (A)140
Current Transformer Current Ratio (A)200/5
Motor Protector or Thermal Overload Relay Setting Current Reference Value (A)140
Current - Time Conversion Device Setting Value (A)5.2
ModelJJ1-90
Control Motor Power (kW)90
Rated Operating Current (A)167
Current Transformer Current Ratio (A)300/5
Motor Protector or Thermal Overload Relay Setting Current Reference Value (A)2.8
Current - Time Conversion Device Setting Value (A)4.2
ModelJJ1-110
Control Motor Power (kW)110
Rated Operating Current (A)207
Current Transformer Current Ratio (A)300/5
Motor Protector or Thermal Overload Relay Setting Current Reference Value (A)3.5
Current - Time Conversion Device Setting Value (A)5.2
ModelJJ1-132
Motor Control Power (kW)132
Rated Operating Current (A)248
Current Transformer Current Ratio (A)400/5
Reference Setting Current for Motor Protector or Thermal Overload Relay (A)3.1
Setting Value of Current-Time Conversion Device (A)4.5
ModelJJ1-160
Motor Control Power (kW)160
Rated Operating Current (A)300
Current Transformer Current Ratio (A)400/5
Reference Setting Current for Motor Protector or Thermal Overload Relay (A)3.8
Setting Value of Current-Time Conversion Device (A)5.2
ModelJJ1-180
Motor Control Power (kW)180
Rated Operating Current (A)331
Current Transformer Current Ratio (A)600/5
Reference Setting Current for Motor Protector or Thermal Overload Relay (A)2.8
Setting Value of Current-Time Conversion Device (A)4.2
ModelJJ1-200
Motor Control Power (kW)200
Rated Operating Current (A)367
Current Transformer Current Ratio (A)600/5
Reference Setting Current for Motor Protector or Thermal Overload Relay (A)3.1
Setting Value of Current-Time Conversion Device (A)4.5
ModelJJ1-220
Motor Control Power (kW)220
Rated Operating Current (A)404
Current Transformer Current Ratio (A)600/5
Reference Setting Current for Motor Protector or Thermal Overload Relay (A)3.4
Setting Value of Current-Time Conversion Device (A)4.9
ModelJJ1-250
Motor Control Power (kW)250
Rated Operating Current (A)459
Current Transformer Current Ratio (A)800/5
Reference Setting Current for Motor Protector or Thermal Overload Relay (A)2.9
Setting Value of Current-Time Conversion Device (A)4.2
ModelJJ1-280

Requirement confirmation

Application, rating, quantity and drawings are checked first.

Factory matching

Supplier capacity, certificates and production slot are reviewed.

Order transaction

Confirm commercial terms, sign the commercial contract, and confirm the related document checklist.

Shipment control

Packing photos, inspection records and delivery status are tracked.