Terminal electrical appliances, self-resetting overvoltage and undervoltage protector products are mainly applicable to new intelligent protection electrical appliances. The product adopts a modular standard design. When the power supply line has overvoltage, undervoltage, loss of voltage or phase failure, the protector can quickly and safely cut off the circuit to prevent abnormal voltage from entering the terminal electrical appliances.

Surprise on inquiry

Product highlights

  • Smart Communication Support
  • Engineering Application Compatibility
  • Stable and reliable operation
  • Easy system integration

Model

Main Product Parameters

CategorySwitchgearSecondary CategoryAuto-reset Overvoltage and Undervoltage Protector
ParametersRated working current: 32-80A; Pole number: 1PN/3PN; Product size: 1PN 27mm 3PN 54mm

Product details

Function and Purpose

The OUVR-2G resettable overvoltage and undervoltage protector is a new generation of intelligent protection electrical equipment. The product adopts a modular standard design. When the power supply line has overvoltage, undervoltage, loss of voltage, or phase failure, the protector can quickly and safely cut off the circuit to prevent abnormal voltage from entering the terminal electrical equipment and causing accidents. When the voltage returns to the normal value, the protector will automatically reconnect the circuit within the specified time, ensuring the normal operation of the terminal electrical equipment in an unattended environment.

Detail Description

Parameters:
Rated Operating Current: 32-80A
Number of poles: 1PN/3PN
Product Dimensions: 1PN 27mm 3PN 54mm

Detailed Parameters

Parameter CategoryParameter ItemParameter Value
Product ModelOUV-2G
Rated Voltage (V)AC230V (1P+N)
AC400V (3P+N)
Rated Current (A)32, 40, 50, 63, 80
Number of Poles1P+N, 3P+N
Overvoltage Action Cut-off Value (V)275V>>
Overvoltage Action Recovery Value (V)253V
Undervoltage Action Cut-off Value (V)161V<<
Undervoltage Action Recovery Value (V)196V
Delay Reset Reconnection Time (s)30s±10
Electrical Life (times)10000
Mechanical Life (times)50000
Environmental Temperature (℃)-35°C~+70°C
Altitude (m)≤3000m
Pollution LevelLevel 2
Installation CategoryCategory II, III
Installation TypeTH35-7.5 type steel installation rail installation

Requirement confirmation

Application, rating, quantity and drawings are checked first.

Factory matching

Supplier capacity, certificates and production slot are reviewed.

Order transaction

Confirm commercial terms, sign the commercial contract, and confirm the related document checklist.

Shipment control

Packing photos, inspection records and delivery status are tracked.